[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"doc-seo-398522-105":3,"detail-sidebar-cat-0-en-105":81,"doc-detail-398522-en":131},{"code":4,"msg":5,"data":6},0,"ok",{"site_id":7,"language":8,"slug":9,"title":10,"keywords":11,"description":12,"schema_data":13,"social_meta":74,"head_meta":76,"extra_data":78,"updated_unix":80},105,"en","heat-flow-calculations-application-note-tsi-124-us","Heat Flow Calculations Application Note TSI-124 (US)","","Application note TSI-124 (US) explains how to calculate air-coil heat flow using upstream and downstream measurements of temperature, humidity, and flow in duct conditions. It provides step-by-step instrument setup, including referencing flow to standard air density and selecting heatflow calculations for real-time displayed values. The note derives sensible heat flow (dry heat), latent heat flow (moisture-state change), and total heat flow, then demonstrates how to compute the sensible heat factor using example conditions in both Imperial and Metric units.",{"@graph":14,"@context":73},[15,34,56],{"@type":16,"itemListElement":17},"BreadcrumbList",[18,23,27,31],{"item":19,"name":20,"@type":21,"position":22},"https://docshare.wps.com","Home","ListItem",1,{"item":24,"name":25,"@type":21,"position":26},"https://docshare.wps.com/document/","Document",2,{"item":28,"name":29,"@type":21,"position":30},"https://docshare.wps.com/document/research-report/","Research & Report",3,{"item":32,"name":10,"@type":21,"position":33},"https://docshare.wps.com/document/heat-flow-calculations-application-note-tsi-124-us/398522/",4,{"url":32,"name":10,"@type":35,"image":36,"author":41,"headline":10,"publisher":44,"fileFormat":47,"inLanguage":8,"description":12,"dateModified":48,"datePublished":49,"encodingFormat":47,"isAccessibleForFree":50,"interactionStatistic":51},"DigitalDocument",{"url":37,"@type":38,"width":39,"height":40},"https://docshare.wps.com/thumbnails/heat-flow-calculations-application-note-tsi-124-us/398522.png","ImageObject",300,407,{"name":42,"@type":43},"Emma Wilson","Person",{"url":19,"name":45,"@type":46},"DocShare","Organization","application/pdf","2026-11-03","2026-09-27",true,{"@type":52,"interactionType":53,"userInteractionCount":55},"InteractionCounter",{"@type":54},"ViewAction",14,{"@type":57,"mainEntity":58},"FAQPage",[59,65,69],{"name":60,"@type":61,"acceptedAnswer":62},"How does the TSI-124 instrument determine heat flow?","Question",{"text":63,"@type":64},"It calculates heat flow from temperature, humidity, and flow measurements taken upstream and downstream of the coil in the duct. The results are based on the provided sensible heat, latent heat, and total heat equations.","Answer",{"name":66,"@type":61,"acceptedAnswer":67},"Why must flow be referenced to standard air density conditions?",{"text":68,"@type":64},"The calculations require flow measurements to correspond to standard air density. Setting the instrument to Standard within the Actual/Standard Setup menu ensures the correct reference for the heat flow computations.",{"name":70,"@type":61,"acceptedAnswer":71},"What is the sensible heat factor (SHF) and how is it used?",{"text":72,"@type":64},"SHF equals sensible heat divided by total heat in the air. The document computes SHF as SHF = QS/QT using calculated QS and QT from both temperature difference and humidity ratio change.","https://schema.org",{"og:url":32,"og:type":75,"og:title":10,"og:site_name":45,"og:description":12},"article",{"robots":77,"canonical":32},"index,follow",{"doc_id":79,"site_id":7},398522,1790828114,{"code":4,"msg":82,"data":83},"success",[84,88,92,96,101,106,111,115,120,123,127],{"id":22,"doc_module":4,"doc_module_name":25,"category_name":85,"show_sort_weight":86,"slug":87},"Story & Novel",90,"story-novel",{"id":26,"doc_module":4,"doc_module_name":25,"category_name":89,"show_sort_weight":90,"slug":91},"Literature",80,"literature",{"id":33,"doc_module":4,"doc_module_name":25,"category_name":93,"show_sort_weight":94,"slug":95},"Exam",70,"exam",{"id":97,"doc_module":4,"doc_module_name":25,"category_name":98,"show_sort_weight":99,"slug":100},5,"Comic",60,"comic",{"id":102,"doc_module":4,"doc_module_name":25,"category_name":103,"show_sort_weight":104,"slug":105},6,"Technology",50,"technology",{"id":107,"doc_module":4,"doc_module_name":25,"category_name":108,"show_sort_weight":109,"slug":110},7,"Healthcare",40,"healthcare",{"id":112,"doc_module":4,"doc_module_name":25,"category_name":29,"show_sort_weight":113,"slug":114},8,30,"research-report",{"id":116,"doc_module":4,"doc_module_name":25,"category_name":117,"show_sort_weight":118,"slug":119},9,"Religion & Spirituality",20,"religion-spirituality",{"id":118,"doc_module":4,"doc_module_name":25,"category_name":121,"show_sort_weight":118,"slug":122},"World Cup","world-cup",{"id":124,"doc_module":4,"doc_module_name":25,"category_name":125,"show_sort_weight":124,"slug":126},10,"Lifestyle","lifestyle",{"id":128,"doc_module":4,"doc_module_name":25,"category_name":129,"show_sort_weight":97,"slug":130},19,"General","general",{"code":4,"msg":82,"data":132},{"doc_id":79,"user_id":133,"nickname":42,"user_avatar":134,"doc_module":4,"category_id":112,"category_name":29,"doc_title":10,"doc_description":12,"doc_content":135,"file_id":136,"file_url":137,"file_type":138,"file_size":139,"view_count":55,"is_deleted":4,"is_public":22,"is_downloadable":22,"audit_status":22,"page_count":33,"language":140,"language_code":8,"site_id":7,"html_lang":8,"table_of_contents":141,"faqs":142,"seo_title":143,"seo_description":12,"update_tm":144,"read_time":124,"preview_page_count":33,"preview_urls":145},3848291630094,"https://eur-avatar.wpscdn.com/davatar_085a072bc5b1113ac321206ff7593b45","HEAT FLOW CALCULATIONS  \nAPPLICATION NOTE TSI-124 (US)  \nThe instrument calculates heat flow by making temperature, humidity, and flow measurements upstream and downstream of the coil in the duct. The following steps and calculations are utilized to make the heat flow measurement:  \n􀁸 Flow measurements must be referenced to standard air density conditions. Set the instrument to Standard within the Actual/Standard Setup menu.  \n􀁸 Select HEATFLOW under the applications menu.  \n􀁸 The current upstream measurements of temperature, humidity, and flow are displayed. Highlight the desired measurement and hit the measurement key. This will update the reading. The flow rate will be calculated using either the thermal anemometer or pitot tube depending if the TA probe is attached.  \n􀁸 Select Downstream to make readings downstream of the coil.  \n􀁸 The unit will display real time values based on the temperature and humidity readings from the probe.  \nThe Equations used for the calculations are described below.  \nSensible Heat Flow  \nSensible heat is dry heat. It causes a change in temperature in a substance, but not a change in the moisture content of that substance.  \nQS = 60cp􀁕q􀀧t (English units) OR QS = cp􀁕q􀀧t/3600 (metric units)  \nwhere QS = sensible heat flow in Btu/hr (kW)  \ncp = specific heat in Btu/lb 􀁱 F = 0.2388 Btu/lb 􀁱 F (1.0048 kJ/kg K)  \n􀁕 = air density at standard conditions = 0.075 lb/ft3 (1.202 kg/m3 )  \nq = measured air flow in ft3/min (m3/hr) (assuming flow is the same at first and second measurement location)  \n􀀧t = temperature difference in 􀁱 F (􀁱 C) (difference between first and second  \nmeasurement location) Replacing constant values gives:  \nQS = 1.0746q􀀧t (English units) OR QS = 1.21q􀀧t/3600 (metric units)  \nTSI and TSI logo are registered trademarks ofTSI Incorporated.  \n\n| Latent Heat Flow\u003Cbr>Latent heat is the heat that when supplied to, or removed from, a substance there is a change in the moisture content of the substance (change in state), but the temperature of that substance does not change.\u003Cbr>QL = 60hfg􀁕q􀀧W (English units) OR QL = hfg􀁕q􀀧W/3600 (metric units)\u003Cbr>where QL = latent heat flow in Btu/hr (kW)\u003Cbr>hfg = latent heat of vaporization of water in Btu/lb = 1060 Btu/lb (2,465.56 kJ/kg)\u003Cbr>􀁕 = air density at standard conditions = 0.075 lb/ft3 (1.202 kg/m3 ) q = measured air flow in ft3/min (m3/hr)\u003Cbr>􀀧W = humidity ratio difference in lb water/lb dry air (kg water/kg dry air) (difference in water content of air between first and second measurement location)\u003Cbr>Replacing constant values gives:\u003Cbr>QL = 4770q􀀧W (English units) OR QL = 0.8287q􀀧W (metric units) |\n| --- |\n| Total Heat Flow\u003Cbr>Total heat is the sum of latent heat and sensible heat.\u003Cbr>QT = QS + QL\u003Cbr>where QT = total heat flow in Btu/hr (kW)\u003Cbr>QS = sensible heat flow in Btu/hr (kW) QL = latent heat flow in Btu/hr (kW) |\n\nSensible Heat Factor  \nThe sensible heat factor equals sensible heat divided by total heat in the air.  \nGiven at measurement location 1 (conditions inside room):  \ndry bulb temperature t1 = 76 􀁱 F %RH1 = 49.0%(􀁉1 = .490) barometric pressure = 29.921 in. Hg  \nGiven at measurement location 2 (conditions of supply air entering room):  \ndry bulb temperature t2 = 53 􀁱 F %RH2 = 88.0%(􀁉2 = .880) flow rate q = 15,000 std ft3/min  \nFind: sensible heat flow QS, latent heat flow QL, total heat flow QT, and sensible heat factor SHF.  \nSensible heat flow QS  \nQS = 1.0746q􀀧t = 1.0746 (15000)(|53-76|) = 370,737 Btu/h of heat removal  \nLatent heat flow QL  \nQL = 4770q􀀧W , so we need to find W1 and W2.  \nW = 0.62198pws (td)/(29.921-pws (td))  \npws (td) = (􀁉1)(pws (t))  \nDefinitions of terms used to calculate W:  \npws (td) = saturation pressure of the air stream at the dew point temperature (inches Hg) pws (t) = saturation pressure of the air stream at ambient temperature (inches Hg)  \n􀁉 = humidity (expresses as a value between 0-1, not as %RH)  \nTo find W1:  \npws (t1) = pws (76 􀁱 F) = 0.90532 in. Hg  \npws (td1) = (􀁉1)(pws (t1)) = (0.490)(0.90","cbCaieTss7H5PpzW","https://ap.wps.com/l/cbCaieTss7H5PpzW","pdf",420592,"English","# Heat Flow Measurement Setup\n## Upstream and Downstream Reading Workflow\n# Calculation Equations\n## Sensible Heat Flow (QS)\n## Latent Heat Flow (QL)\n## Total Heat Flow (QT)\n# Sensible Heat Factor (SHF)\n## Example 1: Imperial Units\n## Example 2: Metric Units","[{\"question\":\"How does the TSI-124 instrument determine heat flow?\",\"answer\":\"It calculates heat flow from temperature, humidity, and flow measurements taken upstream and downstream of the coil in the duct. The results are based on the provided sensible heat, latent heat, and total heat equations.\"},{\"question\":\"Why must flow be referenced to standard air density conditions?\",\"answer\":\"The calculations require flow measurements to correspond to standard air density. Setting the instrument to Standard within the Actual/Standard Setup menu ensures the correct reference for the heat flow computations.\"},{\"question\":\"What is the sensible heat factor (SHF) and how is it used?\",\"answer\":\"SHF equals sensible heat divided by total heat in the air. The document computes SHF as SHF = QS/QT using calculated QS and QT from both temperature difference and humidity ratio change.\"}]","Heat Flow Calculations Application Note TSI-124 (US) | PDF",1790482818,[146,150,154,158],{"page_no":22,"url":147,"width":148,"height":149},"https://res-academy.cache.wpscdn.com/upload/kdocshare/2026-11-16/7ad0283636ab91ffd2f396159810cd98.webp",983,1272,{"page_no":26,"url":151,"width":152,"height":153},"https://res-academy.cache.wpscdn.com/upload/kdocshare/2026-11-16/07eebed448a094ab2da9fec116446ee1.webp",982,1270,{"page_no":30,"url":155,"width":156,"height":157},"https://res-academy.cache.wpscdn.com/upload/kdocshare/2026-11-16/0ffa5c35ee99dae4e917664b4da759a3.webp",981,1269,{"page_no":33,"url":159,"width":160,"height":161},"https://res-academy.cache.wpscdn.com/upload/kdocshare/2026-11-16/a7d57f322ddaa2f37994be4204a32dec.webp",980,1268]